What's App:+86 139 0307 8125 E-mail:repsun1@xierli.com
PRODUCT DETAILS
Features
Datasheet
|
Model |
REP-BC25T1+T2-440-1S |
|
The SPD according to IEC/EN 61643-11 |
I+II/T1+T2 |
|
Nominal AC voltage(Un)
|
400Vac(50/60Hz)
|
|
Maximum continuous voltage(Uc) |
440Vac |
|
Lightning impulse current(10/350μs) limp (L-PE, N-PE) |
25kA/50kA |
|
Specific energy(L-N)/(N-PE)(W/R)
|
156.25kJ/ohms/312.50kJ/ohms
|
|
Nominal discharge current(8/20μs) ln(L-PE, N-PE) |
25kA/50kA |
|
Maximum discharge current(8/20μs) lmax(L-PE, N-PE) |
100kA |
|
Response time |
≤100ns |
|
Voltage protection level Up @ln |
≤2.0kV |
|
Follow current extinguishing capability a.c. Ifi (L-N/N-PE) |
25kA rms/100A rms |
|
Follow current limitation/Selectivity |
No tripping of a 32 A gG fuse up to 25kArms(prosp) |
|
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic |
763V/120min-withstand
|
|
Temporary overvoltage(TOV)(L-N)(UT)-Characteristic |
1200V/120ms.-withstand |
|
Let-Through-Energy in combination with an MOV S20K275(Iimp=2.5...25kA) |
<0.5J |
|
Short-circuit current rating Isscr
|
25kArms
|
|
Backup fuse(only required if not already provided in mains)
|
≤315A gL/gG
|
|
Remote alarm contact |
NC/C, |
|
Remote alarm contact capability Un/In |
AC:250/0.5A DC:250V/0.1A; 75V/0.5A |
|
Remote alarm contact connecting wire |
Max. 1.5mm² or #16AWG |
|
Operating temperature range |
-40℃...+80℃ |
|
Fault indicator |
Light-off: Normal ; Light-on: Failure |
|
Cross-sectional area(min) |
1.5mm²solid/flexible |
|
Cross-sectional area(max) |
35mm²flexible |
|
For mounting on |
35mm DIN rail |
|
Enclosure material |
Red thermoplastic, UL 94 V-0 |
|
Degree of protection |
IP20 |
|
Size |
4 modules |