REP-MS25T1+T2-1300-5S

Product Details
Features
Combination T1+T2 SPD, enabling zero-clearance installation with downstream Type 2 SPD
Specifically designed for higher voltage systems to prevent hazards caused by  direct or indirect lightning current impacts, providing effective protection for numerous industrial applications;
For power equipment in wind turbine / photovoltaic (PV) systems, our SPD fully meets market demands
It is recommended to equip a 200A fuse or backup protector, with its voltage matched to the transformer box voltage.

Datasheet

Model REP-MS25T1+T2-1300-5S
The SPD according to IEC/EN 61643-11 I+II/T1+T2
Nominal AC voltage(Un) 800Vac
Maximum continuous voltage(Uc) 1200Vac
Lightning impulse current(10/350μs) Iimp 12.5kA
Nominal discharge current(8/20μs) In 12.5kA
Voltage protection level Up 4.5kV
Response time tA ≤100ns
Transient overvoltage test voltage (TOV) ≥1730VAC
Varistor voltage (1mA) 1620V
Backup fuse 200AgL/gG
Remote alarm signal NC contact (Optional) Yes☑ No☐
Operating temperature range -40℃...+80 ℃
Altitude ≤2000m
Pollution Degree Class D
Work/Fault indicator Green: Normal ; Red: Failure
Cross-sectional area (min.) 6mm²flexible
Cross-sectional area (max.) 35mm²flexible
For mounting on 35mm DIN rail
Enclosure material Red thermoplastic,UL94 V-0
Degree of protection IP20
Module width 144mm
Dimensions(mm) Diagram

                                                                

                       Side                                   Front
       Diagram