(T2 Surge Protector)REP-MP40 Series

PRODUCT DETAILS

Features

● Type2 surge protector SPD.
● Fast response time(≤25ns) , low voltage protection level.
● Reliable safety due to double integrated disconnectors with double protections.
● Optional to use without a back up fuse.
● Failure indication window, remote alarm terminal optional

Datasheet

Parameter

Specification
Type REP-MP40T2-XXX-XS
The SPD according to IEC/EN 61643 II/T2
Maximum continuous operating voltage(Uc)[L-N] 385Vac 275Vac
Nominal discharge current(8/20μs)(In) 40kA
Maximum discharge current(8/20μs)(Imax) 80kA
Voltage protection level(Up)[L-N] ≤1.8kV ≤1.5kV
Response time 25ns[L-N/PE]/100ns[N-PE]
Operating temperature range -40℃~+80℃
Remote alarm contact Remote alarm contact optional
Degree of protection IP20
Failure indication Green: Normal ; Red: Failure
Enclosure material Thermoplastic; extinguishing degree UL94-V0
Technical feature Double integrated disconnection devices with double protections